The fire protection system of a mutual water company shall be constructed to conform with currently accepted engineering practices, and shall comply with the following construction standards:

(a) The flows set forth in Section 14315 shall be calculated on the basis of a residual pressure of 20 p.s.i.g. in the distribution system under flowing conditions.

(b) Fire hydrants shall be attached to the distribution systems at the locations designated by the entity responsible for their use for firefighting purposes. Any new mains to which a hydrant may be attached shall not be less than six inches in diameter.

(c) Each separately operated water system shall not have less than two independent sources of supply.

Status: in_force · Read it on the official government site

About this page: Statute text is reproduced from official government publishers via the Open US Law dataset (Vaquill AI, snapshot v2026.08, CC BY 4.0). Primary legislative text like this is public domain under the government-edicts doctrine (Georgia v. Public.Resource.Org, 2020). We link every section back to its official source so you can verify it independently.