4.1-37-06. Transfer hose requirements

Official statutory text

4.1-37-06. Transfer hose requirements

1. Any transfer hose utilized at an anhydrous ammonia storage facility:

a. Which is a liquid transfer hose and is not drained of liquid upon completion of

transfer operations must be equipped with an approved shutoff valve at the

discharge end.

b. Must have a hydrostatic relief valve or equivalent must be installed in each

section of hose or pipe in which liquid ammonia can be isolated between shutoff

valves to relieve the pressure that could develop from the trapped liquid. If an

equivalent pressure relief device is used, the maximum accumulated pressure

possible within the system may not exceed the limits of the system. A hydrostatic

relief valve must be installed between each pair of valves in which liquid is

trapped. The start-to-discharge pressure setting of the relief valve must not be

less than three hundred fifty pounds per square inch [2413.18 kilopascals] gauge

nor more than four hundred pounds per square inch [2757.92 kilopascals] gauge.

c. Must have etched, cast, or impressed on the outer coating all of the following:

(1) The words "ANHYDROUS AMMONIA".

(2) The maximum working pressure of the transfer hose.

(3) The name of the manufacturer of the hose.

(4) The date of manufacture or the expiration date of the hose.

d. Which is cut, scraped, cracked, or weathered so that the inner white cord is

visible must be replaced. A transfer hose with an expiration date printed on the

hose must be replaced prior to that date. Transfer hoses without an expiration

date must be replaced as follows:

(1) Rayon hoses must be replaced within two years of the date of manufacture.

(2) Nylon hoses must be replaced within four years of the date of manufacture.

(3) Steel-reinforced hoses must be replaced within six years of the date of

manufacture.

2. Notwithstanding the replacement dates determined under subdivision d of

subsection 1 for transfer hoses with or without an expiration date, an additional year

must be allowed for replacement of transfer hoses in order to take into account delays

in the original installation of transfer hoses.

Status: in_force · Read it on the official government site

Need a lawyer in North Dakota?

Find a North Dakota lawyer
About this page: Statute text is reproduced from official government publishers via the Open US Law dataset (Vaquill AI, snapshot v2026.08, CC BY 4.0). Primary legislative text like this is public domain under the government-edicts doctrine (Georgia v. Public.Resource.Org, 2020). We link every section back to its official source so you can verify it independently.